Operations Manager
Capture sample
Results vs limits
| Date | Site | Point | Parameter | Value | Limit | Result |
|---|---|---|---|---|---|---|
| 2026-10-03 | Clanwilliam WTW | Final water | Turbidity | 0.6 NTU | ≤1 | PASS |
| 2026-10-03 | Clanwilliam WTW | Final water | Free chlorine | 0.21 mg/L | 0.3–5 | FAIL |
| 2026-10-02 | Citrusdal WTW | Reticulation – School | E. coli | 0 cfu/100mL | ≤0 | PASS |
| 2026-10-02 | Citrusdal WTW | Final water | pH | 7.4 | 5–9.7 | PASS |
| 2026-10-01 | Clanwilliam WTW | Raw water | Colour | 42 mg/L Pt-Co | ≤15 | FAIL |
| 2026-10-01 | Graafwater Reservoir | Outlet | Turbidity | 1.8 NTU | ≤1 | FAIL |
Indicative limits — verify against the current SANS 241 edition.